Performance Standard: IEC60502.4; GB12706.4. Based on rubber memory – pre-expanded, inserted plastic tubing. Installation: pull off tubing, rubber shrinks automatically to wrap cable. No professional tools, no fire, long‑term radial pressure, excellent waterproof sealing.
For 0.6/1kV cables – 1, 4 and 5 cores
| Type / Order Number | Name | Cable Range (mm²) |
|---|---|---|
| 1 Core | ||
| 1kVWLT 1 ×25-50 | Termination for 1kV 1 core cable | 25-50 |
| 1kVWLT 1 ×70-120 | Termination for 1kV 1 core cable | 70-120 |
| 1kVWLT 1 ×150-240 | Termination for 1kV 1 core cable | 150-240 |
| 1kVWLT 1 ×300-400 | Termination for 1kV 1 core cable | 300-400 |
| 4 Cores | ||
| 1kVWLT 4 ×25-50 | Termination for 1kV 4 core cable | 25-50 |
| 1kVWLT 4 ×70-120 | Termination for 1kV 4 core cable | 70-120 |
| 1kVWLT 4 ×150-240 | Termination for 1kV 4 core cable | 150-240 |
| 1kVWLT 4 ×300-400 | Termination for 1kV 4 core cable | 300-400 |
| 5 Cores | ||
| 1kVWLT 5 ×25-50 | Termination for 1kV 5 core cable | 25-50 |
| 1kVWLT 5 ×70-120 | Termination for 1kV 5 core cable | 70-120 |
| 1kVWLT 5 ×150-240 | Termination for 1kV 5 core cable | 150-240 |
| 1kVWLT 5 ×300-400 | Termination for 1kV 5 core cable | 300-400 |
For 0.6/1kV cables – 1, 4 and 5 cores
| Type / Order Number | Name | Cable Range (mm²) |
|---|---|---|
| 1 Core | ||
| 1kVWLJ 1 ×25-50 | Straight through joint for 1kV 1 core cable | 25-50 |
| 1kVWLJ 1×70-120 | Straight through joint for 1kV 1 core cable | 70-120 |
| 1kVWLJ 1×150-240 | Straight through joint for 1kV 1 core cable | 150-240 |
| 1kVWLJ 1 ×300-400 | Straight through joint for 1kV 1 core cable | 300-400 |
| 4 Cores (3+1) | ||
| 1kVWLJ 4×25-50 | Straight through joint for 1kV 4 core cable (3+1) | 25-50 |
| 1kVWLJ 4 ×70-120 | Straight through joint for 1kV 4 core cable (3+1) | 70-120 |
| 1kVWLJ 4 ×150-240 | Straight through joint for 1kV 4 core cable (3+1) | 150-240 |
| 1kVWLJ 4 ×300-400 | Straight through joint for 1kV 4 core cable (3+1) | 300-400 |
| 5 Cores | ||
| 1kVWLJ 5 ×25-50 | Straight through joint for 1kV 5 core cable | 25-50 |
| 1kVWLJ 5 ×70-120 | Straight through joint for 1kV 5 core cable | 70-120 |
| 1kVWLJ 5 ×150-240 | Straight through joint for 1kV 5 core cable | 150-240 |
| 1kVWLJ 5 ×300-400 | Straight through joint for 1kV 5 core cable | 300-400 |
1kV indoor/outdoor terminations and joints – test results
| Test Item | Standard Requirement | Test Result | Note |
|---|---|---|---|
| 1min Power frequency test | 4kV 1min no flash over, no strike | 4kV 1min combination sample no flash, no strike | Pass |
| Cyclic load test | 5h heating, conductor temp 95°C, 3h cooling – 3 cycles | Subjected to 3 cycles | Remarked by next test |
| 4h Power frequency test | 2.4kV 4h no flash over, no strike | 2.4kV 4h combination sample no strike, no flash | Pass |