PO Non-shrinkable Tubing
0.6/1kV Termination Straight Joint

0.6/1kV Heat Shrinkable Termination
and Straight Through Joint of Cable 2, 3, 4 & 5 Core Configurations

Suitable for 1kV cable termination & straight joint process, classified into 2, 3, 4 and 5 cores. High mechanical strength, swift shrink without cracks, heat shrink accessories thwart burn, wide cross‑section range, increased UV and weathering stability, unlimited shelf life and allows immediate reenergizing.

High mechanical strength
Shrink swiftly, no cracks
Heat shrink accessories can thwart burn
Wide cross section range, suitable for all types of connectors
Increased UV and weathering stability
Unlimited shelf life and allows immediate reenergizing

Termination – Order Reference

For 1kV 2, 3, 4 and 5 core cables

Type / Order Number Name Cable Range (mm²)
2 Cores
1kV RST -2/0 Termination for 1kV 2 cores cable 10-16
1kV RST -2/1 Termination for 1kV 2 cores cable 25-50
1kV RST -2/2 Termination for 1kV 2 cores cable 70-120
1kV RST -2/3 Termination for 1kV 2 cores cable 150-240
1kV RST -2/4 Termination for 1kV 2 cores cable 300
3 Cores
1kV RST -3/0 Termination for 1kV 3 cores cable 10-16
1kV RST -3/1 Termination for 1kV 3 cores cable 25-50
1kV RST -3/2 Termination for 1kV 3 cores cable 70-120
1kV RST -3/3 Termination for 1kV 3 cores cable 150-240
1kV RST -3/4 Termination for 1kV 3 cores cable 300
4 Cores (3+1)
1kV RST -4/0 Termination for 1kV 4 cores cable (3+1) 10-16
1kV RST -4/1 Termination for 1kV 4 cores cable (3+1) 25-50
1kV RST -4/2 Termination for 1kV 4 cores cable (3+1) 70-120
1kV RST -4/3 Termination for 1kV 4 cores cable (3+1) 150-240
1kV RST -4/4 Termination for 1kV 4 cores cable (3+1) 300
5 Cores (3+2, 4+1)
1kV RST -5/0 Termination for 1kV 5 cores cable (3+2,4+1) 10-16
1kV RST -5/1 Termination for 1kV 5 cores cable (3+2,4+1) 25-50
1kV RST -5/2 Termination for 1kV 5 cores cable (3+2,4+1) 70-120
1kV RST -5/3 Termination for 1kV 5 cores cable (3+2,4+1) 150-240
1kV RST -5/4 Termination for 1kV 5 cores cable (3+2,4+1) 300

Straight Joint – Order Reference

For 1kV 2, 3, 4 and 5 core cables

Type / Order Number Name Cable Range (mm²)
2 Cores
1kV RSJ -2/0 Straight through joint for 1kV 2 cores cable 10-16
1kV RSJ -2/1 Straight through joint for 1kV 2 cores cable 25-50
1kV RSJ -2/2 Straight through joint for 1kV 2 cores cable 70-120
1kV RSJ -2/3 Straight through joint for 1kV 2 cores cable 150-240
1kV RSJ -2/4 Straight through joint for 1kV 2 cores cable 300
3 Cores
1kV RSJ -3/0 Straight through joint for 1kV 3 cores cable 10-16
1kV RSJ -3/1 Straight through joint for 1kV 3 cores cable 25-50
1kV RSJ -3/2 Straight through joint for 1kV 3 cores cable 70-120
1kV RSJ -3/3 Straight through joint for 1kV 3 cores cable 150-240
1kV RSJ -3/4 Straight through joint for 1kV 3 cores cable 300
4 Cores (3+1)
1kV RSJ -4/0 Straight through joint for 1kV 4 cores cable (3+1) 10-16
1kV RSJ -4/1 Straight through joint for 1kV 4 cores cable (3+1) 25-50
1kV RSJ -4/2 Straight through joint for 1kV 4 cores cable (3+1) 70-120
1kV RSJ -4/3 Straight through joint for 1kV 4 cores cable (3+1) 150-240
1kV RSJ -4/4 Straight through joint for 1kV 4 cores cable (3+1) 300
5 Cores (3+2, 4+1)
1kV RSJ -5/0 Straight through joint for 1kV 5 cores cable (3+2,4+1) 10-16
1kV RSJ -5/1 Straight through joint for 1kV 5 cores cable (3+2,4+1) 25-50
1kV RSJ -5/2 Straight through joint for 1kV 5 cores cable (3+2,4+1) 70-120
1kV RSJ -5/3 Straight through joint for 1kV 5 cores cable (3+2,4+1) 150-240
1kV RSJ -5/4 Straight through joint for 1kV 5 cores cable (3+2,4+1) 300

Technical Index

1kV indoor/outdoor terminations and joints – test results

Test Item Standard Requirement Test Result Note
1min Power frequency test 4kV 1min no flash over, no strike Pass – 4kV, 1min combination sample no flash, no strike Pass
Cyclic load test 5h heating, conductor temperature 95°C, 3h cooling – 3 cycles Subjected to 3 cycles Remarked by next test
4h Power frequency test 2.4kV 4h no flash over, no strike 2.4kV 4h combination sample no strike, no flash over Pass